Protect equipment from high PV Open
Circuit Voltage at Low Temperatures
Size the PV array for maximum energy
harvest
Every PV array can now be sized without being limited
by the high open-circuit voltages present at low temperatures.
The Apollo Solar LTOB automatically switches modules
out of the circuit if the temperature falls below the
specified point.
Simple, Reliable Operation
The LTOB removes 1 module from the 6 module string keeping
Voc under 140v. When the temperature falls below 10OC
(50OF) the LTOB turns on and the top module is switched
out of the circuit so the Voc drops to 120 volts. The
5 module string is below the 140volt limit down to -40O.
When the temperature rises, the LTOB turns off and the
module is switched back into the circuit.
Fast, Easy Installation
The Apollo Solar LTOB units are supplied with an adhesive
tape on the back side. Just peel off the backing layer
and stick the LTOB and Temperature Sensor to the back
of the PV module to be cut from the string. Simply snap
the MC connectors together. At normal or high temperatures
the LTOB connects straight through and the PV array
functions normally.